Body Size (W x H x D) |
96 x 48 x 100 mm. |
Accuracy Under Surrounding Temperature 25±5℃ |
Thermocouple |
K, J, E, T, R, S (Set value ±0.3 or ±0.2℃, whichever is greater) ±1 Digit |
Thermocouple |
B (Set value ±0.3 or ±3℃, which is greater) ±1 Digit (However B input 0 - 500℃ is outside Guranteed Accuracy range) |
RTD |
(Set value ±0.3 or ±0.8℃, which is greater) ±1 Digit |
Voltage / Current |
(±0.3% of Scaling Width or ±1 Digit, whichever is greater) ±1 Digit |
Input |
Thermocouple |
K, J, E, T, R, S (JIS, IEC, DIN Standard)B |
RTD |
Pt100Ω (JIS, IEC, DIN Standard), JPt100Ω (Old JIS) |
Linear Input Voltage |
DC1 - 5 V |
Linear Input Current |
DC4 - 20 mA |
Output |
Relay Connection |
(2A/250VAC, 2A/30VDC, COSφ=1, 1c point) |
SSR Drive Voltage |
DC 12 V Standard, Load Resitance 250Ω Min Standard (Special Order DC5 V, Load Resitance 200Ω Min Standard) |
Current Output |
4~20mA Load Resitance 400Ω Max Standard 187 Resolution (Special Order 2907 Resolution) |
Transmission |
Measured value output as DC4~20 mA on External Output (Load Resistance 400Ω max 2907 Resolution) (Control Output can not be included with Current Output) |
Control Style |
PID auto tuning, PID Manual, P, On/Off control Proprotional Band (PB) = 0~200% of Temperature range, Integral Time (l) = 0 ~ 3999 sec Derivative Time (D) = 0 ~ 3999 sec Proportional Time (PT) = 0.5 ~ 64 sec Anti Reset windup (ARW) = PB 1 ~ 100% or PB ON/OFF Sensitivity (DIF) = 0.0 ~ 99.9℃ |
Temperature Range |
K |
-100 ~ 1200 ℃ (-99 ~199.9 ℃) |
E |
-200 ~ 1000 ℃ |
J |
-100 ~ 800 ℃ |
T |
-150 ~ 300 ℃ |
R |
100 ~ 1600 ℃ |
B |
500 ~ 1800 ℃ |
S |
100 ~ 1600 ℃ |
C |
-200 ~ 400 ℃ (-199.9 ~400 ℃) |
G |
-200 ~ 600 ℃ (-199.9 ~600 ℃) |
IRt/c, NI |
0 ~400 ℃, -50 ~300 ℃ |
Alarm Function |
Max. 3 Alarm (1a) Types of temperature alarms, choose from Sensor / Heater Abnormalities, includes Heater (Current Display Function) * AR33 Max. 2 Alarms |
Communication Function |
Compatible with RS-485 signal format |
EEPROM |
1,000,00 Write / Eease Cycle |
Power supply |
AC 100 ~ 240V -10%, 15% 50/60Hz Free Power (Special Order: AC 24 V±10%, DC 24 V ±10%) |
Operating Temperature |
-10 ~ 60 ℃ (Assuming no dew condensation) |
Storage Temperature |
-20 ~ 70 ℃ (Assuming no dew condensation) |
Operating Humidity |
RH 40 ~ 85 % (Assuming no dew condensation) |
Power Comsumption |
12 VA max |
Dielectric Resistance |
100MΩMis DC500V, Between Output relay terminals and power supply terminals |
High Potencial Rating |
AC 2300 V for 1 Min, Between Output relay terminals and power supply terminals |
Earthquake- proof |
10~55Hz, All Ampritude 0.3mm Each X,Y,Z Direction for 1 hour |
Shock-proof |
18.6m/s2 (20G) Each X, Y, Z Direction for 5 times |
Standard |
Safety Standard: IEC61010-1Contamination Level 2 Installation Category Ⅱ EMC: EMI: EN50081-2/EN55011 Class A, Group 1 EMS: EN50082-2 |